banner
Products
Our pricing policy ensures high quality products at affordable prices.
Cutout Fuse 27kv (PRW-38)

Cutout Fuse 27kv (PRW-38)

CUT-OUT Gama 20 kV a 36 kV- Circuito Principal 200 A- Ith 8 kA.- Montaje Vertical- Tubo Fusible de 100 A- Norma CEI 282-;
Basic Info
Model NO. PRW-38
Standard IEC IEEE
Transport Package Cartons Pallets Wooden Case
Specification IEC282-2 IEEEc37-41
Trademark OEIpower
Origin China Nanyang
HS Code 85351000
Production Capacity 100000
Product Description
CUT-OUT

 

Gama 20 kV a 36 kV- Circuito Principal 200 A- Ith 8 kA.- Montaje Vertical- Tubo Fusible de 100 A- Norma CEI 282-2- Tubo Fusible compatible con losestándar norteamericanos.- Este modelo permite el montajede la Autoválvula directamentesobre la escuadra de fijación.- Eslabones fusible:de 2 Amp. a 100 Amp.- Porcelana de color gris, efectoAntivandálico.-- Montaje sencillo gracias a sustornillos de fijación anti-giro.- No es necesaria ningunaherramienta para cambiar eleslabónLa base cortacircuitos en "V" monta aisladores de columna conarmaduras metálicas externas y línea de fuga en función de los nivelesde contaminación I-III-IV asignados.Su diseño permite el accionamiento por pértiga desde una posición mascómoda para la maniobra, al conseguir un ángulo de 45º con respecto ala base de sujección.Incorpora un tubo fusible con capacidad para eslabones de hasta 100A, y es totalmente intercambiable con los modelos de una columna ymodelos de otros fabricantes.El interior del tubo portafusible está constituido por un recubrimientovegetal lo que le confiere un poder de extinción superior a otrosmodelos (según fabricante).El Seccionalizador en "V" monta aisladores de columna conarmaduras metálicas externas y línea de fuga en función de los nivelesde contaminación I-III-IV asignados.Su diseño permite el accionamiento por pértiga desde una posición mascómoda para la maniobra, al conseguir un ángulo de 45º con respecto ala base de sujección.

Cutout Fuse 27kv (PRW-38)

Gama:15 , 24 y 36 kV12 - 25 - 40 - 63 -100 - 140 ANúmero de Defectos: 1 , 2 (Estándar) , 3.Tiempo de Regeneración : Min. 30s.Principales Características :Dispositivo Autoalimentado. Utilización conjunta con Interruptores automáticos.Importante reducción en los costes derivados de mano de obra y sustitución de fusible de los Cut-Outconvencionales derivados de fallos transitorios, ocasionados por tormentas eléctricas , accidentesvegetales , etc...Ausencia de Arcos y desgaste en los contactos.Reutilización del equipo tras su rearme manual y acoplamiento en su base.TYPE "OEI" "PRW" STANDARD CUTOUT DISTRIBUTION TECHNICAL SPECIFICATION
The Fuse Cutout type DHE was developed to operate in overhead distribution systems rated at 12-15 kV and 15-27,kV or 27-38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI PRW can be applied on all three-phase system rated at or below the maximum operational rating of the cutout. In highly polluted environments or environments with high levels of salinity, a cutout may be used with a higher nominal rating than
that of the system where it is being installed, where the insulator will have a greater leakage distance to ground, allowing for
increased safety against discharge. For an even better protection against abrasions, the hardware may be supplied in stainless

Cutout Fuse 27kv (PRW-38)


steel. The fuse cutout type OEI PRW has attachment hooks in aluminum.
The Fuseholder has a stainless steel flipper, which associated with a spring doesn't allow the fuse link to be subject to traction
forces of over 3 Kgf, especially during closing. This me chanism also allows for high speed fuse link separation. The fuse cutout
type OEI PRW allows for the insertion of the fuse tube in a precise man ner and always in perfect alignment, due to the large distance
between the grunion pocket. Lower contact, silver-to-silver, provide du el current path, independent of hinge pivot. Stainless-steel
back-up springs prevent arcing when tube rises in hinge during recoil. The fuse cutout type OEI PRW may be transformed into a DICONNECT up to 300 A, by simply changing the fuse tube for an electrolytic copper blade.
The DHE Fuse Cutouts conform to ANSI and IEC standards, with independent tests performed At:
CPRI Always use quality fuse links. Only they can assure excellent performance.
Performance Characteristic
Applied standardIEC60282-2
Catalog number
Nominal system voltage kV11
Rated Frequency Hz50
Rated m aximum(design) voltage12
Rated Continuous current A-RMS100
Rated Interrupting current asymmetrical/symmetrical A-RMS12000/8000
BIL 1.2x50 µs kV-peak125
Minimum critical impulse flashover voltage(CFO)KV peak140
Dry withstand voltage kV-RMS42
Wet withstand voltage kV-RMS36
Creepage distance to group Min.mm372
Minimum creepage factor of insulator (Creepage Distance/arcing distance)N/A
Performance Characteristic
Applied standardIEEE C37.42-2009
Catalog number
Nominal system voltage kV22
Rated Frequency Hz50
Rated m aximum(design) voltage27
Rated Continuous current A-RMS100
Rated Interrupting current asymmetrical/symmetrical A-RMS12000/8000
BIL 1.2x50 µs kV-peak125
Minimum critical impulse flashover voltage(CFO)KV peak140
Dry withstand voltage kV-RMS42
Wet withstand voltage kV-RMS36
Creepage distance to group Min.mm320
Minimum creepage factor of insulator (Creepage Distance/arcing distance)2
Performance Characteristic
Applied standardIEEE C37.42-2009
Catalog number
Nominal system voltage kV33
Rated Frequency Hz50
Rated m aximum(design) voltage38
Rated Continuous current A-RMS100
Rated Interrupting current asymmetrical/symmetrical A-RMS8000/5000
BIL 1.2x50 µs kV-peak150
Minimum critical impulse flashover voltage(CFO)KV peak165
Dry withstand voltage kV-RMS70
Wet withstand voltage kV-RMS60
Creepage distance to group Min.mm650
Minimum creepage factor of insulator (Creepage Distance/arcing distance)2.3

Cutout Fuse 27kv (PRW-38)

Cutout Fuse 27kv (PRW-38)

Cutout Fuse 27kv (PRW-38)

Send inquiry